Control Ability - Manufacturers of tachometers, control panel meters, monitors, timing systems, sensors and vending control systems.
Control Ability - Manufacturers of tachometers, control panel meters, monitors, timing systems, sensors and vending control systems.

Data Sheet

<< BACK TO OVERVIEW
Part No.: SAM130
Product: Programmable Process Indicator / Digital Panel Meter
Product Range: Process Control Panel Meters

SAM130 - Programmable Process Indicator / Digital Panel Meter

Specifications

SUPPLY: 12 or 24V DC (11-15 or 19-30)V DC min. & max.
AUXILIARY OUTPUTS: 9V DC or 15V DC @ 30 ma (12 or 24V models)
ACCURACY: Determined by program, ±1 digit, normally better than 0.1%
RANGE: 0-9999
DISPLAY: 12.5 mm LCD
INPUTS: 0-10V DC or 0-20 ma DC or 4-20 ma, Potentiometer Options (and most sub multiples of these down to 1V & 1mA)
OUTPUT FREQUENCY: 1 kHz for 10V input when SF1 = 12500 (0.5V pulse)
UPDATE TIME: Variable 150 mSec - 2 seconds
ZERO OFFSET: 1 digit per 1000 units of scale
ZERO OFFSET ADJUSTMENT: 0-9999 digits
DIMENSIONS: 96 mm x 48 mm x 135 mm
PANEL CUT OUT: 91 mm x 43 mm
WEIGHT: 0.5 Kg
OUTPUT OPTIONS: 0-10V DC (Max. load 10mA), 4-20mA DC (Max. load = 500R), Relays (two rated at 0.1A @ 24V AC)

The SAM130 for 12 or 24V DC systems.

The SAM130 is a four digit panel mounting process indicator / digital panel meter with LCD display which may be programmed to display process information from signals of 0-10 Volts or 4-20 mA. a series of 12 parameters are programmable by the front panel push buttons or from a separate detachable keypad. Optional dual alarm relays or an analogue output are also available.

Programmable features include display scaling, hold time and update time and decimal point may be selected. Auto scaling features are included for use where the display required for an incoming analogue input is known.

Operation from 0-10V or 4-20 mA is program selectable.

When the relay or analogue output options are included the relay set points and analogue full scale output are set in the parameter program.

An output pulse with a frequency proportional to the 0-10V input is available as standard.

The instrument may be used to measure standard 0-10V or 4-20mA process signals and display in units which refer to the variable being monitored. E.g. pressure, temperature, height, position, speed, time, voltage, current, etc.

The optional relays are suitable for alarm or control purposes and the optional 0-10V or 4-20 ma outputs are available for recording data logging ore control purposes.

Counter